 MTL5113P AND 5114P FAILSAFE SWITCH/PROXIMITY DETECTOR INTERFACE
LFD option
With the MTL5113P/5114P, a fail-safe switch/proximity detector located in the hazardous area can control an isolated fail-safe electronic output. The MTL5113P units provide line-fault detection alarm contacts. The MTL5113P and MTL5114P are for use with P + F TUV approved fail-safe sensors.
Hazardous area
Safe area
1kW
6 5 4 3 +2 1
7 8 9 10 11 12 13 14
+
Fail-safe output
10kW or switch inputs, sistors must be fitted *MTL5113P only
LFD* Vs Vs+ 20 to 35V dc
SPECIFICATION
(For both MTL5113P and MTL5114P unless otherwise indicated.) See also common specification Number of channels One Location of switches Zone 0, IIC, T6 hazardous area Div. 1, Group A hazardous location Location of proximity detector Zone 0, IIC, T4-6, hazardous location Div 1, Group A, hazardous location Voltage applied to sensor 8.6V dc max from 1k Input/output characteristics
Input value in sensor circuit Fail-safe output Operation LFD contacts (MTL5113x only) CLOSED
Terminal 1 2 7 8 11 12 13 14
Function Input -ve Input +ve Output -ve Output +ve LFD (MTL5113P only) LFD (MTL5113P only) Supply -ve Supply +ve
MTL5113P, MTL5114P 2.9mAMTL5113P, MTL5114P Is<1.9mA & Is>5.1mA MTL5113P Is<50A MTL5113P Is>6.6mA
ON
Normal
OFF
Normal
CLOSED
Power dissipation within unit MTL5113P MTL5114P 1.4W 1.2W at 20V dc 1.5W 1.3W at 24V dc 2.0W 1.4W at 35V dc Safety description 9.7V, 30mA, 70mW, Ci=33nF, Li=0mH Weight 160g approx.
Note: switch-type sensors must be fitted with resistors as shown
OFF OFF
Broken line Shorted line
OPEN OPEN
Note: Is = sensor current
Fail-safe electronic output Output on: > 22.8V Output off: 0V dc, max <5V dc Load: 2.4k to 10k Maximum on-state current: 11mA Short-circuit current: 25mA Line fault detection (LFD), MTL5113P only Relay output for line fault (contacts open when line fault detected) Switch characteristics: 0.3A 110V ac/dc, 1A 30V dc, 30W/33VA LED indicators Amber: one provided for output status, ON when fail-safe output is energised Green: one provided for power indication Red: one provided for LFD, ON when line fault is detected (MTL5113P only) Power requirements, Vs MTL5113P MTL5114P 80mA 70mA at 20V dc 70mA 60mA at 24V dc 65mA 45mA at 35V dc
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283 AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899 ASIA PACIFIC Tel: +65 487 7887 Fax: +65 487 7997 E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
June 2004


▲Up To Search▲   

 
Price & Availability of MTL5113P

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X